FE [.]XXXXXXXX2X00[XX][/[ TH/humidity | TH/latesthumidity | TH/temperature | TH/latesttemp | TH/led | firmware | subtype | ]]
FE
read-only,
floating point
Humidity read by the chip at high resolution (˜13
bits). Unit is % relative humidity. Negative values indicate
a condensing condition. Conversion takes about one
second.
read-only,
floating point
Latest measured humidity. Reading this node will never
trigger a combined humidity/temperature conversion. Intended
for use after a previous read of the TH/temperature
node or in conjunction with /simultaneous/iblss.
read-only,
floating point
Temperature read by the chip at high resolution
(˜13 bits). Units are selected from the invoking
command line. See owfs(1) or owhttpd(1) for
choices. Default is Celsius. Conversion takes about one
second.
read-only,
floating point
Latest measured temperature. Reading this node will never
trigger a combined humidity/temperature conversion. Intended
for use after a previous read of the TH/humidity node
or in conjunction with /simultaneous/iblss.
write-only,
yes-no
Switches the indicator LED on/off.
read-only,
ascii
Firmware version of the Smart Slave displayed as major.major
number. Firmware versions of the SS-WALL-TH before 1.4 had
known issues with humidity reporting.
read-only,
ascii
Subtype of the Smart Slave. Currently only possible value is
"TH" signifying an SS-WALL-TH drywall
temperature/humidity sensor.
None.
https://www.ibuttonlink.com/products/ss-wall-th
http://www.owfs.org
Paul Alfille <[email protected]> Jan Kandziora <[email protected]>